After-sales Service: | 7/24 on-Line Service |
---|---|
Warranty: | 5 Years |
Nature of Source Flow: | Passive inverter |
Samples: |
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Technical Data
Model
|
SUN-5K
-SG04LP3-EU
|
SUN-6K
-SG04LP3-EU |
SUN-8K
-SG04LP3-EU |
SUN-10K
-SG04LP3-EU |
SUN-12K
-SG04LP3-EU |
Battery Input Data
|
|||||
Battery Type
|
Lead-acid or Lithium-ion
|
||||
Battery Voltage Range (V)
|
40-60
|
||||
Max. Charging Current (A)
|
120
|
150
|
190
|
210
|
240
|
Max. Discharging Current (A)
|
120
|
150
|
190
|
210
|
240
|
External Temperature Sensor
|
Yes
|
||||
Charging Curve
|
3 Stages / Equalization
|
||||
Charging Strategy for Li-Ion Battery
|
Self-adaption to BMS
|
||||
PV String Input Data
|
|||||
Max. DC Input Power (W)
|
6500
|
7800
|
10400
|
13000
|
15600
|
Rated PV Input Voltage (V)
|
550 (160-800)
|
||||
Start-up Voltage (V)
|
160
|
||||
MPPT Voltage Range (V)
|
200-650
|
||||
Full Load DC Voltage Range (V)
|
350-650
|
||||
PV Input Current (A)
|
13+13
|
26+13
|
|||
Max. PV I (A)
|
17+17
|
34+17
|
|||
No.of MPP Trackers
|
2
|
||||
No.of Strings per MPP Tracker
|
1+1
|
2+1
|
|||
AC Output Data
|
|||||
Rated AC Output Active Power (W)
|
5000
|
6000
|
8000
|
10000
|
12000
|
Max AC Output Active Power (W)
|
5500
|
6600
|
8800
|
11000
|
13200
|
AC Output Rated Current (A)
|
7.6/7.2
|
9.1/8.7
|
12.1/11.6
|
15.2/14.5
|
18.2/17.4
|
Max AC Output Current (A)
|
8.4/8
|
10/9.6
|
13.4/12.8
|
16.7/15.9
|
20/19.1
|
Max. Three-phase Unbalanced Output Current (A)
|
11.4/10.9
|
13.6/13
|
18.2/17.4
|
22.7/21.7
|
27.3/26.1
|
Max Output short circuit current (A)
|
75
|
||||
Max. Continuous AC Passthrough (A)
|
45
|
||||
Peak Power (off grid)
|
2 time of rated power, 10 S
|
||||
Power Factor
|
0.8 leading to 0.8 lagging
|
||||
Output Frequency and Voltage
|
50/60Hz; 3L/N/PE 220/380, 230/400Vac
|
||||
Grid Type
|
Three Phase
|
||||
Total Harmonic Distortion (THD)
|
<3% (of nominal power)
|
||||
DC Current Injection
|
<0.5% In
|
||||
Efficiency
|
|||||
Max. Efficiency
|
97.60%
|
||||
Euro Efficiency
|
97.00%
|
||||
MPPT Efficiency
|
99.90%
|
The following illustration shows basic application of this inverter.
It also includes following devices to have a Complete running system.
- Generator or Utility
- PV modules
Suppliers with verified business licenses